# Install the MGA0800 air conditioning module on a totem

> How to unpack, inspect, mount and wire the MGA0800 air conditioning module on the cabinet door of an outdoor digital totem, including power and RS485.

The MGA0800 air conditioning module mounts on the totem cabinet door and is fixed with M5 screws. This page covers unpacking, mechanical mounting and electrical connections (power, RS485 and the alarm dry contact).

<Note>
  The installation diagram in the manual is for reference only. Determine the actual installation scheme according to the real operating environment.
</Note>

## Unpacking and inspection

<Steps>
  <Step title="Prepare tools">
    Prepare a knife and scissors, and wear protective gloves.
  </Step>

  <Step title="Remove the packaging">
    Remove the wrapping film and packing belt, then the carton, and take out the air conditioner.
  </Step>

  <Step title="Check the contents">
    Check the accessory list and accessory bags in the carton and confirm the air conditioner model is correct.
  </Step>
</Steps>

<Warning>
  * After unpacking, keep the unit **upright**. Do not lay it horizontally or upside down.
  * Check carefully for damage or oil stains. If the unit shows obvious deformation or oil stains, contact the manufacturer immediately.
</Warning>

* If the product will not be installed right away or must be transported elsewhere, repack it after inspection.
* Recycling the packaging materials is recommended.

## Mechanical installation

**Tool required:** Phillips screwdriver.

<Steps>
  <Step title="Prepare the cutout">
    Choose the cutout location on the cabinet according to the drilling diagram, remove the shaded area and make the mounting hole.
  </Step>

  <Step title="Fix the unit">
    Bring the unit flange against the cabinet door and fix it firmly to the mounting surface with M5 screws.
  </Step>

  <Step title="Check the installation">
    Check that the unit is level and firmly fixed.
  </Step>
</Steps>

<Warning>
  * Check that the condensate drain path is clear and not blocked.
  * When positioning the mounting hole, make sure no internal components block the air inlet and outlet inside the cabinet. Keep a horizontal distance of **more than 150 mm** between them; otherwise return air can short-circuit and cooling becomes poor.
  * Handle the unit carefully to avoid knocks and scratches to its surface coating.
</Warning>

## Electrical installation

### Power input port

3-pin connector: **L**, **N**, **PE**.

| Item | Port | Definition |
| - | - | - |
| Live | L | 220 V AC power input, L |
| Neutral | N | 220 V AC power input, N |
| Earth | PE | Protective earth |

### Alarm output and signal port

5-pin connector: **RS485A**, **RS485B**, **NC**, **COM**, **NO**.

| Item | Port | Definition |
| - | - | - |
| RS485 communication interface (+) | RS485A | RS485 communication port (+) |
| RS485 communication interface (-) | RS485B | RS485 communication port (-) |
| General alarm dry contact (NO) | NO | Normally open when there is no alarm |
| General alarm dry contact (COM) | COM | Common |
| General alarm dry contact (NC) | NC | Normally closed when there is no alarm |

<Tip>
  After installation, go through the pre-start checks on the [Operation](/en/aer-conditionat/functionare) page.
</Tip>


## Related topics

- [MGA0800 air conditioning module for outdoor totems](/en/aer-conditionat/prezentare.md)
- [MGA0800 air conditioner operation, display and parameters](/en/aer-conditionat/functionare.md)
- [Air conditioning module alarms, troubleshooting and upkeep](/en/aer-conditionat/depanare-mentenanta.md)
- [Installing and Operating Outdoor Digital Totem Kiosks](/en/operare/echipamente-outdoor.md)
- [Operating Environment Requirements for Digital Totems](/en/instalare/mediu-operare.md)


This documentation is built and hosted on [Mintlify](https://mintlify.com), a developer documentation platform.