# Air conditioning module alarms, troubleshooting and upkeep

> MGA0800 air conditioning module alarms, possible fault causes and how to fix them, plus the schedule of periodic checks and cleaning to keep it running well.

The MGA0800 air conditioning module reports problems through alarm codes on the display and, for some alarms, through the alarm dry contact. This page explains the alarms, possible fault causes, fixes and the periodic maintenance schedule.

## Alarms

All alarms reset automatically once the cause is gone.

| Alarm | Condition | Reset | Dry contact output |
| - | - | - | - |
| High temperature | Cabinet temperature is above the setting | Automatic | Yes |
| Low temperature | Cabinet temperature is below the setting | Automatic | No |
| T1 temperature sensor | Short or open circuit on the cabinet temperature sensor cable | Automatic | No |
| T2 temperature sensor | Short or open circuit on the evaporator temperature sensor cable | Automatic | No |
| T3 temperature sensor | Short or open circuit on the condenser temperature sensor cable | Automatic | No |
| Evaporator frozen | Evaporator temperature is below 0 °C | Automatic | Yes |
| Frequent high system pressure | System pressure frequently exceeds the setting | Automatic | Yes |
| Controller power failure | No power input to the controller | Automatic | Yes |

## Faults and fixes

<AccordionGroup>
  <Accordion title="Temperature sensor failure">
    | Possible cause | Fix |
    | - | - |
    | Sensor not connected correctly | Check the connectors and reconnect the sensor |
    | Sensor damaged | Replace the sensor |
  </Accordion>

  <Accordion title="High temperature alarm">
    | Possible cause | Fix |
    | - | - |
    | Condenser or evaporator dirty and blocked | Clean the condenser or evaporator |
    | Insufficient cooling capacity | Consult a specialist |
    | Wrong temperature setting | Set the temperature again |
  </Accordion>

  <Accordion title="Frequent high system pressure alarm">
    | Possible cause | Fix |
    | - | - |
    | Condenser or evaporator dirty and blocked | Clean the condenser or evaporator |
    | External fan faulty | Replace the fan |
    | Condenser temperature sensor sends false alarms | Replace the condenser temperature sensor |
  </Accordion>

  <Accordion title="Evaporator frozen alarm">
    | Possible cause | Fix |
    | - | - |
    | Internal air path blocked | Check for obstructions in the internal air path |
    | Internal fan faulty | Repair or replace the fan |
    | Cooling system does not stop | Check whether the unit reached the cooling stop conditions but keeps cooling; if so, inform the manufacturer |
    | Evaporator temperature sensor sends false alarms | Replace the temperature sensor |
  </Accordion>

  <Accordion title="Compressor does not run">
    | Possible cause | Fix |
    | - | - |
    | No cooling demand | Check whether cooling is actually needed |
    | Shutdown delay active | Check whether compressor protection is active |
    | Compressor cable not connected correctly | Check the compressor cable and reconnect it |
    | Compressor protection switch or motor faulty | Check the protection switch and replace it if faulty; if the motor is faulty, replace the compressor |
  </Accordion>

  <Accordion title="Internal fan does not run">
    | Possible cause | Fix |
    | - | - |
    | Internal fan faulty | Replace the fan |
    | Internal fan cable not connected correctly | Check the cable and reconnect it |
    | Fan stuck | Check for anything blocking the fan and clear it |
  </Accordion>

  <Accordion title="External fan does not run">
    | Possible cause | Fix |
    | - | - |
    | External fan faulty | Replace the external fan |
    | Operating condition not met | Check whether the operating condition is met |
    | External fan cable not connected correctly | Check the cable and reconnect it |
    | External fan stuck | Check for anything blocking the fan and clear it |
  </Accordion>

  <Accordion title="Fan makes abnormal noise">
    | Possible cause | Fix |
    | - | - |
    | Blades damaged or bearing worn | Replace the damaged fan |
    | Blades touch other objects | Check and refit the fan |
  </Accordion>

  <Accordion title="Heater does not run">
    | Possible cause | Fix |
    | - | - |
    | Heater faulty | Replace the heater |
    | Heater cables not connected correctly | Check the heater cables and reconnect them |
    | Operating condition not met | Check whether the operating condition is met |
  </Accordion>
</AccordionGroup>

## Periodic maintenance

Careful maintenance keeps the unit performing well and preserves its normal service life. Carry out the following:

| No. | Check / maintenance | Interval |
| - | - | - |
| 1 | Check for alarms | 6 months |
| 2 | Check that the fans rotate normally | 6 months |
| 3 | Check that the compressor runs normally | 6 months |
| 4 | Check for obvious noise or vibration | 6 months |
| 5 | Clean the internal and external air inlets and outlets | 6 months |
| 6 | Clean the heat exchangers | 1 year |
| 7 | Check the power supply and communication cables | 1 year |

<Tip>
  If the problem persists after these checks, contact the [support team](/en/suport/contact).
</Tip>


## Related topics

- [MGA0800 air conditioning module for outdoor totems](/en/aer-conditionat/prezentare.md)
- [Install the MGA0800 air conditioning module on a totem](/en/aer-conditionat/instalare.md)
- [MGA0800 air conditioner operation, display and parameters](/en/aer-conditionat/functionare.md)
- [Installing and Operating Outdoor Digital Totem Kiosks](/en/operare/echipamente-outdoor.md)
- [Troubleshooting Common Issues on Your Digital Totem](/en/operare/depanare.md)


This documentation is built and hosted on [Mintlify](https://mintlify.com), a developer documentation platform.